Voltage Drop Calculator

Use our free voltage drop calculator to estimate electrical losses in DC, single-phase AC, and three-phase circuits. Compare copper AWG wire sizes, cable lengths, and voltage drop percentages to plan more efficient wiring.

Circuit & Wire Details

Estimate copper conductor voltage loss for DC and AC circuits.

DC supply voltage

Uses approximate copper DC resistance adjusted for temperature. AC results use resistance-only estimates: no cable reactance, power factor or harmonics. The tool does not check wire ampacity.

Your Voltage Drop Result

Estimated conductor losses for your selected circuit.

Estimated voltage drop—Approximate resistive loss
Voltage drop (%)—
Estimated load voltage—
Drop per 100 ft—
Thinnest listed AWG within target—
Approx. cable power loss—
Wire resistance—
Change the inputs to compare voltage drop.

A result within 3% or 5% is not proof of electrical code compliance. Verify conductor ampacity, insulation, temperature limits, protective devices and installation rules separately.

AWG Wire Size Comparison

Ten copper conductor sizes, compared at your chosen current, length and temperature.

Wire sizeΩ / 1,000 ftDrop (V)Drop (%)Target

Scroll horizontally on smaller screens. Resistance values are illustrative and can differ by conductor construction and manufacturer.

How to Use the Voltage Drop Calculator

Calculate estimated wire losses in three easy steps.

STEP 01

Enter Wire Details

Select your copper AWG wire size and enter the one-way cable length in feet or meters. Choose the conductor temperature for your calculation.

STEP 02

Set Circuit Values

Enter the load current and source voltage. Select DC, single-phase AC, or three-phase AC, then choose a 3% or 5% planning target.

STEP 03

Review Your Results

Check the calculated voltage loss, percentage drop, estimated load voltage, and cable power loss. Compare different conductor sizes in the AWG table.

Understanding Your Results

Learn what each calculation means for your electrical circuit.

Voltage Drop

Shows the estimated voltage lost through conductor resistance. Higher current, longer cable runs, and greater wire resistance increase this value.kW)

Percentage Voltage Drop

Displays voltage loss as a percentage of source voltage. Compare the result with your selected planning target to evaluate circuit efficiency.

Voltage at Load

Estimates the remaining voltage after subtracting conductor losses from the source voltage. Actual equipment voltage may differ under operating conditions.

Cable Power Loss

Estimates electrical power dissipated as heat in the conductors. It helps illustrate how wire resistance affects energy efficiency.

AWG Wire Size Recommendation

Identifies the thinnest wire in the calculator’s available AWG list that meets your selected voltage drop target. The comparison uses your cable length, circuit current, copper temperature, and supply voltage. Results also show wire resistance and voltage drop per 100 feet, making it easier to compare conductor options. This is a voltage-drop-only recommendation; you must check ampacity, insulation temperature limits, protection, and applicable electrical codes before selecting a cable.

How Voltage Drop Is Calculated

Voltage drop occurs when electrical current passes through a conductor with resistance. The amount of loss depends on wire size, cable distance, current, and conductor temperature.

Our calculator uses approximate copper resistance values for a simplified electrical voltage drop calculation.

DC Voltage Drop Formula

Voltage Drop (V) = 2 × Length (ft) × Current (A) × Resistance (Ω/1,000 ft) ÷ 1,000

The factor of two accounts for the outgoing and returning conductors.

Single-Phase AC Formula

Voltage Drop (V) ≈ 2 × Length × Current × Resistance ÷ 1,000

Three-Phase AC Formula

Voltage Drop (V) ≈ √3 × Length × Current × Resistance ÷ 1,000

For three-phase systems, enter the line-to-line source voltage.

These AC formulas are resistance-only approximations. They do not account for cable reactance, power factor, or harmonics.

Voltage Drop Percentage

Voltage Drop (%) = Voltage Drop ÷ Source Voltage × 100

Practical Example

Consider a 48V DC electrical circuit with these values:

  • Wire size: 10 AWG copper

  • One-way cable length: 100 ft

  • Load current: 20 A

  • Conductor temperature: 75°C

  • Planning target: 3%

The calculator estimates:

Voltage drop: 4.860 V

Voltage drop percentage: 10.12%

Estimated load voltage: 43.140 V

This exceeds the selected 3% planning target. In the tool’s available comparison, 4 AWG is the thinnest listed conductor that meets the target under these assumptions.

Cable Length: Longer wires have more total resistance. Increasing the one-way conductor distance increases voltage loss when the current, wire size, and other conditions remain unchanged.

Wire Gauge: Larger copper conductors generally have lower resistance. In the AWG system, lower gauge numbers indicate thicker wires, while sizes such as 1/0 and 2/0 are larger still.

Electrical Current: Higher current increases voltage drop across the same conductor. Current also affects resistive heating, making proper wire sizing important for both efficiency and electrical safety.

Conductor Temperature: Copper resistance increases as its temperature rises. This calculator provides approximate resistance estimates at 20°C and 75°C to help illustrate temperature-related differences.

How Wire Size Affects Voltage Drop

Compare conductor losses using these five simple steps.

1. Select Wire Size

Choose copper conductor gauge from available sizes.

2. Enter Cable Length

Measure the one-way distance of your circuit.

3. Add Electrical Load

Enter the expected current and source voltage.

4. Select Circuit Type

Choose DC or the appropriate AC circuit.

5. Compare Losses

Review voltage drop percentages.

Voltage Drop Calculator Wiring Example

Frequently Asked Questions

How do I calculate voltage drop in a wire?

Multiply conductor resistance by current and effective circuit length. For a DC circuit with separate supply and return conductors, the simplified calculation uses twice the one-way distance.

A commonly used design recommendation is approximately 3% for a branch circuit and 5% combined across feeder and branch circuits. These are general efficiency guidelines, not universal mandatory limits. Always check applicable standards and equipment requirements.

Yes. Thicker copper wire generally has lower electrical resistance, which reduces voltage loss when current and cable distance remain the same.

DC voltage drop can be estimated using conductor resistance and current. AC circuits can also be affected by reactance and power factor. This calculator provides simplified resistance-only estimates for both.

Yes, it can estimate resistive voltage losses in solar DC cable runs, battery connections, and other electrical circuits. It does not perform complete PV conductor sizing or safety checks.

The same absolute voltage loss represents a larger percentage of a lower supply voltage. For example, losing 1V in a 12V circuit is a larger percentage than losing 1V in a 48V circuit.

No. The AWG recommendation only considers the selected voltage-drop target. For comprehensive wire-sizing calculations that also consider current-carrying capacity, consult the Southwire Voltage Drop Calculator or a qualified electrical professional.

Related Solar Calculators

Explore these free tools to plan your solar energy system with more detailed estimates.

Estimate solar panels, battery storage, and equipment requirements for an independent energy system.

Calculate battery capacity and backup energy requirements for your solar setup.

Estimate how much electricity your solar array may produce using system size, sunlight conditions, and performance assumptions.

Important: This voltage drop calculator provides approximate conductor resistance calculations only. It does not verify wire ampacity, electrical codes, fault protection, insulation ratings, AC impedance, or the safety of a specific installation. Consult a qualified electrician for final wiring decisions.